Causes and solutions for RTO burner flameout


RTO burners are used for the treatment of organic waste gas. The application industries include coating lines in automobile, shipbuilding, home appliances, containers, etc., and waste gas treatment in production lines such as petrochemical, rubber, coatings, viscose, printing, and enameled wire. It is especially suitable for enterprises that require heat recovery or waste gas treatment in drying lines.


The following focuses on the analysis of the reasons why the burner cannot be started and the treatment methods when it cannot ignite.


Causes and solutions for RTO burner flameout:


A) Is the gas source turned on?


Turn on the gas source.


B) Under normal circumstances, there is no ignition treatment method. (The next issue will focus on the explanation.)


C) Is the solenoid valve activated?


Is the solenoid valve disconnected? When igniting, please pay attention to the sound of the solenoid valve or touch it with your hand to confirm. If there is no action, please check whether there is any error in the solenoid valve wiring.


D) There is flame but no detection.


Is the flame detection UV aged and exceeded the service life? Please update it.


Note: Please confirm that the flame detection UV is in contact with the flame and is not grounded or disconnected when igniting. If the flame electron current is detected to be above the minimum value of 1μA and it cannot ignite, the combustion controller is faulty and please replace it.


  • Brief introduction to what is industrial combustion of burners
  • Boiler room civil engineering structure standards and layout requirements
  • Working principle of gas infrared igniter
  • What is wrong with gas steam boilers that cannot ignite
  • What is the working principle and circuit diagram of natural gas boiler burner
  • Where is the boiler safety valve installed
  • How to clean and replace the burner filter
  • Which companies are suitable for industrial steam boilers
  • Precautions for the operation of horizontal quick-install gas boilers
  • Reasons why gas boilers cannot ignite

Back

Causes and solutions for RTO burner flameout


RTO burners are used for the treatment of organic waste gas. The application industries include coating lines in automobile, shipbuilding, home appliances, containers, etc., and waste gas treatment in production lines such as petrochemical, rubber, coatings, viscose, printing, and enameled wire. It is especially suitable for enterprises that require heat recovery or waste gas treatment in drying lines.


The following focuses on the analysis of the reasons why the burner cannot be started and the treatment methods when it cannot ignite.


Causes and solutions for RTO burner flameout:


A) Is the gas source turned on?


Turn on the gas source.


B) Under normal circumstances, there is no ignition treatment method. (The next issue will focus on the explanation.)


C) Is the solenoid valve activated?


Is the solenoid valve disconnected? When igniting, please pay attention to the sound of the solenoid valve or touch it with your hand to confirm. If there is no action, please check whether there is any error in the solenoid valve wiring.


D) There is flame but no detection.


Is the flame detection UV aged and exceeded the service life? Please update it.


Note: Please confirm that the flame detection UV is in contact with the flame and is not grounded or disconnected when igniting. If the flame electron current is detected to be above the minimum value of 1μA and it cannot ignite, the combustion controller is faulty and please replace it.


RIELLO

Shanghai Qigu Technology Co., LTD
Block I-J, 14th Floor, Greenland Kechuang Building, 201 Ningxia Road, Putuo District, Shanghai
CHINA China,200333
Burner:Contact +08613761094501
Boiler:Contact +08613761094501
Fax :+08613761094501
E-mail:pittsenli@gmail.com


© Qigu Technology – copyright


Navigation

About Us
Burner
Low nitrogen burner
High temperature burner
Special burner
After service
Company
Contact

Networks

International
België/Belgique (Belgium)
Canada
中国 (China)
Hrvatska (Croatia)
Česká Republika (Czech Republic)
France (France)
Deutschland (Germany)
Magyarország (Hungary)
Italia (Italy)
Latvija (Latvia)
Polska (Poland)
România (Romania)
Россия (Russia)
España (Spain)
Slovenija (Slovenia)
United Kingdom
United States

Link

  • riello spare parts
  • plc control cabinets
  • 空压机配件
  • 电气控制柜
  • 利雅路燃烧器