RIELLO
WHATSAPP:+08613761094501
E-MAIL:pittsenli@gmail.com
  • Home
  • About Us
    • About Us
    • Mission
    • R&D Center
    • History
  • Burner
  • Selection
  • Parts
  • Case
  • After service
  • Company
    • Company news
    • Industry News
  • Contact
Riello - Global burner leader brand > Company Information > 公司新闻

公司新闻


Burner system fault detection method


During the use of the burner, due to improper use or external factors such as mechanical wear, various system faults often occur. Today, we will popularize the burner's ignition system fault, engine flameout system fault, burner non-operation system fault, etc. Next, we, Xuanxuan Technology, will take you to understand what the burner system faults are? And how to deal with them! Under the premise that the ignition system fault is normal, the burner is operated three times continuously. If no ignition is found, it should be judged as an ignition system fault. Corresponding routine inspections must be carried out to detect the fault.


(1) Ignition system fault


Under the premise that everything is normal, the burner is operated three times continuously. If no ignition is found, it should be judged as an ignition system fault. Corresponding routine inspections must be carried out to detect the fault.


1. Gas source system fault Routinely check whether the working pressure of natural gas can be maintained normally at 3-5kpa. Too high or too low will cause the problem of non-ignition.


Solution: Adjust the natural gas pressure regulating valve and adjust the working pressure.


2. Air Inlet System Failure: Regularly check the air inlet size. If the air inlet is slightly larger, frequent ignition misfires may occur.

Solution: Reduce the air inlet appropriately, but do not completely close it.


3. Ignition Electrode or Ignition Transformer System Failure: If the ignition transformer fails to ignite, or if the ignition electrode is dirty or incorrectly positioned, an ignition system failure may occur.

Solution: Test the ignition transformer for ignition, clean the ignition electrode, and adjust the ignition distance to maintain 2-3 mm.


4. Gas Valve System Failure: During normal ignition, the valve opens promptly and an audible opening sound is heard. If it fails to open, no flame is generated.

Solution: Regularly check the valve coil and adjust the valve opening.

5. Ignition Controller System Failure: All ignition applications are transmitted by the intelligent controller. A faulty intelligent controller will prevent normal ignition.

Solution: Replace the intelligent controller.


(2) Engine flameout system failure When the burner is running normally, it suddenly goes out. This is an engine flameout system failure.


1. The gas source fluctuates, causing the flame to float and then go out.


Solution: Adjust the working pressure and restart.


2. Flame detector system failure When the flame detection probe is grounded during operation, or when it is very dirty, no normal flame can be detected, indicating that the engine has stopped.


Solution: Adjust the specific position of the probe and clean the probe surface. Restart.


3. Power circuit system failure The power supply fluctuates or is missing a phase, causing the engine to stop during the process.


Solution: Contact the welder to regularly check the power supply and wiring method.


(3) Burner non-operation system failure The burner does not operate after pressing the operation switch button for a long time


1. External interlocking system failure The external temperature or working pressure control cannot reach the operating lower limit; regularly check the temperature or working pressure preset value.


2. The internal structure of the burner has not been locked. When the standard air pressure is too high or too low, the wind pressure switch is normally closed and cannot be found, and the air inlet mechanism is in place, it will be displayed and routine inspections should be carried out step by step.


  • Burner system fault detection method
  • Exhaust Gas Treatment for the Main Incineration Processes of Different Incinerat
  • Various Types of "Air" in Pulverized Coal Boiler Burners
  • Components of a Pure Oxygen Combustion System
  • Industrial Gas Burner Safety Operating Procedures introduce
  • Available Flue Gas Waste Heat Utilization Options
  • Analysis of Factors Affecting Boiler Thermal Efficiency
  • Intelligent Combustion Control Technology for Waste Incinerators
  • A Brief Discussion on "Air Preheater Cold-End Integrated Temperature"
  • What You Need to Know About Burner Selection

Back

Burner system fault detection method


During the use of the burner, due to improper use or external factors such as mechanical wear, various system faults often occur. Today, we will popularize the burner's ignition system fault, engine flameout system fault, burner non-operation system fault, etc. Next, we, Xuanxuan Technology, will take you to understand what the burner system faults are? And how to deal with them! Under the premise that the ignition system fault is normal, the burner is operated three times continuously. If no ignition is found, it should be judged as an ignition system fault. Corresponding routine inspections must be carried out to detect the fault.


(1) Ignition system fault


Under the premise that everything is normal, the burner is operated three times continuously. If no ignition is found, it should be judged as an ignition system fault. Corresponding routine inspections must be carried out to detect the fault.


1. Gas source system fault Routinely check whether the working pressure of natural gas can be maintained normally at 3-5kpa. Too high or too low will cause the problem of non-ignition.


Solution: Adjust the natural gas pressure regulating valve and adjust the working pressure.


2. Air Inlet System Failure: Regularly check the air inlet size. If the air inlet is slightly larger, frequent ignition misfires may occur.

Solution: Reduce the air inlet appropriately, but do not completely close it.


3. Ignition Electrode or Ignition Transformer System Failure: If the ignition transformer fails to ignite, or if the ignition electrode is dirty or incorrectly positioned, an ignition system failure may occur.

Solution: Test the ignition transformer for ignition, clean the ignition electrode, and adjust the ignition distance to maintain 2-3 mm.


4. Gas Valve System Failure: During normal ignition, the valve opens promptly and an audible opening sound is heard. If it fails to open, no flame is generated.

Solution: Regularly check the valve coil and adjust the valve opening.

5. Ignition Controller System Failure: All ignition applications are transmitted by the intelligent controller. A faulty intelligent controller will prevent normal ignition.

Solution: Replace the intelligent controller.


(2) Engine flameout system failure When the burner is running normally, it suddenly goes out. This is an engine flameout system failure.


1. The gas source fluctuates, causing the flame to float and then go out.


Solution: Adjust the working pressure and restart.


2. Flame detector system failure When the flame detection probe is grounded during operation, or when it is very dirty, no normal flame can be detected, indicating that the engine has stopped.


Solution: Adjust the specific position of the probe and clean the probe surface. Restart.


3. Power circuit system failure The power supply fluctuates or is missing a phase, causing the engine to stop during the process.


Solution: Contact the welder to regularly check the power supply and wiring method.


(3) Burner non-operation system failure The burner does not operate after pressing the operation switch button for a long time


1. External interlocking system failure The external temperature or working pressure control cannot reach the operating lower limit; regularly check the temperature or working pressure preset value.


2. The internal structure of the burner has not been locked. When the standard air pressure is too high or too low, the wind pressure switch is normally closed and cannot be found, and the air inlet mechanism is in place, it will be displayed and routine inspections should be carried out step by step.


RIELLO

Shanghai Qigu Technology Co., LTD
Block I-J, 14th Floor, Greenland Kechuang Building, 201 Ningxia Road, Putuo District, Shanghai
CHINA China,200333
Burner:Contact +08613761094501
Boiler:Contact +08613761094501
Fax :+08613761094501
E-mail:pittsenli@gmail.com


© Qigu Technology – copyright


Navigation

About Us
Burner
Low nitrogen burner
High temperature burner
Special burner
After service
Company
Contact

Networks

International
België/Belgique (Belgium)
Canada
中国 (China)
Hrvatska (Croatia)
Česká Republika (Czech Republic)
France (France)
Deutschland (Germany)
Magyarország (Hungary)
Italia (Italy)
Latvija (Latvia)
Polska (Poland)
România (Romania)
Россия (Russia)
España (Spain)
Slovenija (Slovenia)
United Kingdom
United States

Link

  • riello spare parts
  • plc control cabinets
  • 空压机配件
  • 电气控制柜
  • 利雅路燃烧器