Common faults and solutions for gas boiler burners


1. Phenomenon: The ignition rod of the gas boiler burner does not ignite


reason:


1. There is carbon residue and oil stains in the gap between the ignition rods.


2. The ignition rod is broken. Moist. Leakage.


3. The distance between the ignition rods is wrong, too long or short.


4. The insulation skin of the ignition rod is damaged and short-circuited to ground.


5. The ignition cable and transformer are faulty: the cable is disconnected, the connector is damaged, causing a short circuit during ignition; the transformer is disconnected or other faults occur.


Measures: clear, replace with new ones, adjust distance, change wires, replace transformer.


2. Phenomenon: The ignition rod of the gas boiler has sparks but cannot ignite.


reason:


1. The ventilation gap of the cyclone disk is blocked by carbon deposits and the ventilation is poor.


2. The oil nozzle is dirty, clogged or worn.


3. The damper setting angle is too small.


4. The distance between the ignition rod and the front edge of the oil nozzle is inappropriate (too protruding or retracted)


5. The solenoid valve of the oil gun is blocked by debris (small fire oil gun).


6. The oil is too viscous to flow easily or the filter system is clogged or the oil valve is not opened, resulting in insufficient oil suction by the oil pump and low oil pressure.


7. The filter of the oil pump itself is blocked.


8. The oil contains a lot of water (there is an abnormal sound of boiling in the heater).

Measures: Clean; clean first, if not, replace with new one; adjust the size and test; adjust the distance (preferably 3~4mm); disassemble and clean (clean the parts with diesel); check the pipelines, oil filters, and insulation equipment; dismantle Remove the outer screws of the oil pump, carefully remove the outer cover, take out the oil screen inside, and soak it with diesel oil; replace it with new oil and try it.


3. Phenomenon: When the small fire of the gas boiler is normal and turns to a large fire, it goes out or flickers erratically.


reason:


1. The air volume of the fire damper is set too high.


2. The micro switch of the oil valve of the large fire (the group outside the damper) is not set appropriately (the air volume is set to be larger than that of the damper of the large fire).


3. The oil viscosity is too high and difficult to atomize (heavy oil).


4. The distance between the cyclone plate and the oil nozzle is improper.


5. The high-fire oil nozzle is worn or dirty.


6. The heating temperature of the reserve oil tank is too high, causing steam to cause difficulty in oil delivery by the oil pump.


7. The oil in the oil-fired boiler contains water.


Measures: gradually reduce the test; increase the heating temperature; adjust the distance (between 0~10mm); clean or replace; set to about 50°C; change the oil or drain the water.


4. Phenomenon: Gas boiler burner noise increases


reason:


1. The stop valve in the oil circuit is closed or the oil inflow is insufficient, and the oil filter is blocked.


2. The inlet oil temperature is low, the viscosity is too high or the pump inlet oil temperature is too high.


3. The oil pump of the domestic sewage treatment device failed.


4. The fan motor bearing is damaged.


5. The fan impeller is too dirty.


Measures: ① Check whether the valve in the oil pipeline is open, whether the oil filter is working normally, and clean the filter screen of the pump itself. ②Heat the oil or lower the oil temperature. ③Replace the oil pump. ④Replace the motor or bearing. ⑤Clean the fan impeller.


  • Working principle of RTO burner waste gas treatment equipment
  • What factors should be considered when selecting a linear burner
  • Causes and solutions for RTO burner flameout
  • Safety control requirements for boiler gas burners
  • Gas boiler water treatment problem solution
  • What to do if the burner does not ignite
  • Riello burners should be selected according to gas pressure
  • Conditions for shutdown of boiler due to accident
  • What tools are there for boiler burners
  • How to use the burner igniter

Back

Common faults and solutions for gas boiler burners


1. Phenomenon: The ignition rod of the gas boiler burner does not ignite


reason:


1. There is carbon residue and oil stains in the gap between the ignition rods.


2. The ignition rod is broken. Moist. Leakage.


3. The distance between the ignition rods is wrong, too long or short.


4. The insulation skin of the ignition rod is damaged and short-circuited to ground.


5. The ignition cable and transformer are faulty: the cable is disconnected, the connector is damaged, causing a short circuit during ignition; the transformer is disconnected or other faults occur.


Measures: clear, replace with new ones, adjust distance, change wires, replace transformer.


2. Phenomenon: The ignition rod of the gas boiler has sparks but cannot ignite.


reason:


1. The ventilation gap of the cyclone disk is blocked by carbon deposits and the ventilation is poor.


2. The oil nozzle is dirty, clogged or worn.


3. The damper setting angle is too small.


4. The distance between the ignition rod and the front edge of the oil nozzle is inappropriate (too protruding or retracted)


5. The solenoid valve of the oil gun is blocked by debris (small fire oil gun).


6. The oil is too viscous to flow easily or the filter system is clogged or the oil valve is not opened, resulting in insufficient oil suction by the oil pump and low oil pressure.


7. The filter of the oil pump itself is blocked.


8. The oil contains a lot of water (there is an abnormal sound of boiling in the heater).

Measures: Clean; clean first, if not, replace with new one; adjust the size and test; adjust the distance (preferably 3~4mm); disassemble and clean (clean the parts with diesel); check the pipelines, oil filters, and insulation equipment; dismantle Remove the outer screws of the oil pump, carefully remove the outer cover, take out the oil screen inside, and soak it with diesel oil; replace it with new oil and try it.


3. Phenomenon: When the small fire of the gas boiler is normal and turns to a large fire, it goes out or flickers erratically.


reason:


1. The air volume of the fire damper is set too high.


2. The micro switch of the oil valve of the large fire (the group outside the damper) is not set appropriately (the air volume is set to be larger than that of the damper of the large fire).


3. The oil viscosity is too high and difficult to atomize (heavy oil).


4. The distance between the cyclone plate and the oil nozzle is improper.


5. The high-fire oil nozzle is worn or dirty.


6. The heating temperature of the reserve oil tank is too high, causing steam to cause difficulty in oil delivery by the oil pump.


7. The oil in the oil-fired boiler contains water.


Measures: gradually reduce the test; increase the heating temperature; adjust the distance (between 0~10mm); clean or replace; set to about 50°C; change the oil or drain the water.


4. Phenomenon: Gas boiler burner noise increases


reason:


1. The stop valve in the oil circuit is closed or the oil inflow is insufficient, and the oil filter is blocked.


2. The inlet oil temperature is low, the viscosity is too high or the pump inlet oil temperature is too high.


3. The oil pump of the domestic sewage treatment device failed.


4. The fan motor bearing is damaged.


5. The fan impeller is too dirty.


Measures: ① Check whether the valve in the oil pipeline is open, whether the oil filter is working normally, and clean the filter screen of the pump itself. ②Heat the oil or lower the oil temperature. ③Replace the oil pump. ④Replace the motor or bearing. ⑤Clean the fan impeller.


RIELLO

Shanghai Qigu Technology Co., LTD
Block I-J, 14th Floor, Greenland Kechuang Building, 201 Ningxia Road, Putuo District, Shanghai
CHINA China,200333
Burner:Contact +08613761094501
Boiler:Contact +08613761094501
Fax :+08613761094501
E-mail:pittsenli@gmail.com


© Qigu Technology – copyright


Navigation

About Us
Burner
Low nitrogen burner
High temperature burner
Special burner
After service
Company
Contact

Networks

International
België/Belgique (Belgium)
Canada
中国 (China)
Hrvatska (Croatia)
Česká Republika (Czech Republic)
France (France)
Deutschland (Germany)
Magyarország (Hungary)
Italia (Italy)
Latvija (Latvia)
Polska (Poland)
România (Romania)
Россия (Russia)
España (Spain)
Slovenija (Slovenia)
United Kingdom
United States

Link

  • riello spare parts
  • plc control cabinets
  • 空压机配件
  • 电气控制柜
  • 利雅路燃烧器