1. Extinguish the fire after the unstable gas source causes the flame to fluctuate. Treatment method; adjust the pressure and restart;
2. When the flame detector is faulty, the flame detection probe is grounded, or when it is too dirty, the normal flame cannot be detected, and the flame goes out. Treatment method: adjust the position of the probe, clean the surface of the probe, and restart;
3. Circuit failure, unstable power supply or lack of phase, resulting in flameout during the process. Solution: Contact an electrician to check the power supply and wiring.
technical operation
1. Press the main fire start button on the combustion control panel. After the mother fire working indicator light is on for 10 seconds, confirm that the mother fire is lit. If the main fire indicator light goes out within 10 seconds, and the combustion failure alarm buzzer on the combustion control panel sounds, it means that the ignition has failed; wait for 60 seconds and then manually press the fault reset button of the programmer to restart the main fire button;
2. After the main fire is ignited normally, the operator can confirm whether the main fire is ignited through the observation hole of the burner. After confirmation, press the large fire start button on the burner control panel. After a delay of several seconds, after the high fire work indicator light is on, the operator in front of the furnace should slowly open the load regulating ball valve, and at the same time increase the gas-supporting air in proportion until the flame appears. The main blue plus reddish is the best;
3. After the fire is ignited and stabilized, check whether the gas supply pressure of the main pipeline is within the normal range;
4. The fan starts, enters the pre-blowing stage, and checks to confirm that the equipment is in a normal state;
5. Observe the gas and air pressure indications, and confirm that the burner operation permission instructions are given;
6. Press the combustion control button on the combustion control panel, and the combustion controller enters the combustion start program;
7. The ignition task of taking over the Ming mother fire has been completed. The operator should turn off the main fire button on the panel in time, cut off the main fire and keep the fire burning;
8. The operator can adjust the size of the flame (load) at any time according to the process requirements during the burning process of the fire. When the process requires that the fire be turned off for a short time, the operator should turn on the main fire switch to keep the main fire, and then turn off the high fire switch;
9. Adjust the operating handle of the gas valve and air valve, which can be adjusted in stages to ensure that the burner load output meets the process requirements;
10. Shutdown operation: For temporary shutdown, first turn off the fire, then turn off the combustion control switch, and finally turn off the stop button.
1. Extinguish the fire after the unstable gas source causes the flame to fluctuate. Treatment method; adjust the pressure and restart;
2. When the flame detector is faulty, the flame detection probe is grounded, or when it is too dirty, the normal flame cannot be detected, and the flame goes out. Treatment method: adjust the position of the probe, clean the surface of the probe, and restart;
3. Circuit failure, unstable power supply or lack of phase, resulting in flameout during the process. Solution: Contact an electrician to check the power supply and wiring.
technical operation
1. Press the main fire start button on the combustion control panel. After the mother fire working indicator light is on for 10 seconds, confirm that the mother fire is lit. If the main fire indicator light goes out within 10 seconds, and the combustion failure alarm buzzer on the combustion control panel sounds, it means that the ignition has failed; wait for 60 seconds and then manually press the fault reset button of the programmer to restart the main fire button;
2. After the main fire is ignited normally, the operator can confirm whether the main fire is ignited through the observation hole of the burner. After confirmation, press the large fire start button on the burner control panel. After a delay of several seconds, after the high fire work indicator light is on, the operator in front of the furnace should slowly open the load regulating ball valve, and at the same time increase the gas-supporting air in proportion until the flame appears. The main blue plus reddish is the best;
3. After the fire is ignited and stabilized, check whether the gas supply pressure of the main pipeline is within the normal range;
4. The fan starts, enters the pre-blowing stage, and checks to confirm that the equipment is in a normal state;
5. Observe the gas and air pressure indications, and confirm that the burner operation permission instructions are given;
6. Press the combustion control button on the combustion control panel, and the combustion controller enters the combustion start program;
7. The ignition task of taking over the Ming mother fire has been completed. The operator should turn off the main fire button on the panel in time, cut off the main fire and keep the fire burning;
8. The operator can adjust the size of the flame (load) at any time according to the process requirements during the burning process of the fire. When the process requires that the fire be turned off for a short time, the operator should turn on the main fire switch to keep the main fire, and then turn off the high fire switch;
9. Adjust the operating handle of the gas valve and air valve, which can be adjusted in stages to ensure that the burner load output meets the process requirements;
10. Shutdown operation: For temporary shutdown, first turn off the fire, then turn off the combustion control switch, and finally turn off the stop button.