Burner safety interlock protection requirements


Under the following circumstances, the burner shall automatically cut off the fuel supply within a safe time and the system shall be interlocked safely:




(1) When the burner is started, a flame is detected within the pre-blowing time and no flame is detected within the ignition (main) fire safety time.




(2) The flame suddenly goes out when the burner is running.




(3) When there is an abnormal signal of air monitoring (fault of air supply system).




(4) When the gas pressure is lower or higher than the set value.




(5) When the burner is in operation, the burner and its spray gun are rotated or moved without using tools.




(6) When the limiter related to the heating equipment exceeds the limit (such as: pressure, water level, temperature, etc.).




Under the following circumstances, the burner shall automatically cut off the gas supply within a safe time and the system shall be shut down safely, and the burner shall be restarted only after manual reset or cutting off and restoring the power supply. When the burner main switch is touched.


  • What conditions are required for flame treatment combustion systems
  • Energy-saving and consumption-reducing measures for industrial boilers
  • Safety operation procedures for gas boiler burners
  • Brief introduction to what is industrial combustion of burners
  • Boiler room civil engineering structure standards and layout requirements
  • Working principle of gas infrared igniter
  • What is wrong with gas steam boilers that cannot ignite
  • What is the working principle and circuit diagram of natural gas boiler burner
  • Where is the boiler safety valve installed
  • How to clean and replace the burner filter

Back

Burner safety interlock protection requirements


Under the following circumstances, the burner shall automatically cut off the fuel supply within a safe time and the system shall be interlocked safely:




(1) When the burner is started, a flame is detected within the pre-blowing time and no flame is detected within the ignition (main) fire safety time.




(2) The flame suddenly goes out when the burner is running.




(3) When there is an abnormal signal of air monitoring (fault of air supply system).




(4) When the gas pressure is lower or higher than the set value.




(5) When the burner is in operation, the burner and its spray gun are rotated or moved without using tools.




(6) When the limiter related to the heating equipment exceeds the limit (such as: pressure, water level, temperature, etc.).




Under the following circumstances, the burner shall automatically cut off the gas supply within a safe time and the system shall be shut down safely, and the burner shall be restarted only after manual reset or cutting off and restoring the power supply. When the burner main switch is touched.


RIELLO

Shanghai Qigu Technology Co., LTD
Block I-J, 14th Floor, Greenland Kechuang Building, 201 Ningxia Road, Putuo District, Shanghai
CHINA China,200333
Burner:Contact +08613761094501
Boiler:Contact +08613761094501
Fax :+08613761094501
E-mail:pittsenli@gmail.com


© Qigu Technology – copyright


Navigation

About Us
Burner
Low nitrogen burner
High temperature burner
Special burner
After service
Company
Contact

Networks

International
België/Belgique (Belgium)
Canada
中国 (China)
Hrvatska (Croatia)
Česká Republika (Czech Republic)
France (France)
Deutschland (Germany)
Magyarország (Hungary)
Italia (Italy)
Latvija (Latvia)
Polska (Poland)
România (Romania)
Россия (Russia)
España (Spain)
Slovenija (Slovenia)
United Kingdom
United States

Link

  • riello spare parts
  • plc control cabinets
  • 空压机配件
  • 电气控制柜
  • 利雅路燃烧器